Omron MY4-GS DC48 General Purpose Relay - Equivalent & Substitute Parts

Part Overview

The Omron MY4-GS DC48 is a general purpose relay featuring a 4PDT (4 Form C) contact configuration with a 48VDC coil. This relay is classified as obsolete, making identification of suitable substitute components essential for system maintenance, repair, and redesign applications. The MY4-GS series provides reliable switching capability for industrial control circuits requiring multiple independent switching paths.

Substiute Parts

MY4-GS DC48
Omron Automation and SafetyIn Stock: 1078MY4-GS DC48 Datasheet
MY4-GS DC48
Current Part
MY4-GS-R DC48
Omron Automation and SafetyIn Stock: 873MY4-GS-R DC48 Datasheet
MY4-GS-R DC48
MFR Recommended

Key Parameters

Parameter Value
Manufacturer Part Number MY4-GS DC48
Manufacturer Omron Automation and Safety
Series MY
Relay Type General Purpose
Contact Form 4PDT (4 Form C)
Coil Voltage 48VDC
Switching Voltage 250VAC, 220VDC - Max
Coil Type Non Latching
Product Status Obsolete
RoHS Status RoHS Compliant
Moisture Sensitivity Level (MSL) 1 (Unlimited)

Substitute Part Grouping Explanation

The MY4-GS-R DC48 qualifies as a direct substitute for the MY4-GS DC48 based on the following critical parameters:

  • Contact Configuration: Both parts maintain identical 4PDT (4 Form C) contact form
  • Coil Voltage: Both operate at 48VDC
  • Relay Type: Both are general purpose relays with non-latching coil type
  • Switching Voltage Rating: Both support 250VAC and 220VDC maximum switching voltage
  • Series Compatibility: Both belong to the Omron MY series
  • Compliance: The substitute part maintains RoHS3 compliance, exceeding the original RoHS requirement

The primary distinction is the mounting configuration: the MY4-GS-R DC48 is socketable with plug-in quick connect termination, whereas the original MY4-GS DC48 mounting type is not specified. The substitute part is currently in active production status, ensuring long-term availability.

Parameter Comparison

Parameter MY4-GS DC48 (Original) MY4-GS-R DC48 (Substitute)
Manufacturer Part Number MY4-GS DC48 MY4-GS-R DC48
Manufacturer Omron Automation and Safety Omron Automation and Safety
Series MY MY
Relay Type General Purpose General Purpose
Contact Form 4PDT (4 Form C) 4PDT (4 Form C)
Coil Voltage 48VDC 48VDC
Switching Voltage 250VAC, 220VDC - Max 250VAC, 220VDC - Max
Coil Type Non Latching Non Latching
Product Status Obsolete Active
RoHS Status RoHS Compliant ROHS3 Compliant
Contact Rating (Current) Not specified 6 A
Coil Current Not specified 18.8 mA
Must Operate Voltage Not specified 38.4 VDC
Must Release Voltage Not specified 4.8 VDC
Operating Temperature Not specified -55°C ~ 70°C
Contact Material Not specified Silver (Ag)

Engineering Selection Recommendations

The MY4-GS-R DC48 is the appropriate substitute for the obsolete MY4-GS DC48 based on the following factors:

  • Product Continuity: The substitute part is in active production status, ensuring availability for current and future procurement cycles
  • Compliance Enhancement: The MY4-GS-R DC48 meets ROHS3 compliance, providing improved environmental and regulatory alignment compared to the original RoHS Compliant designation
  • Functional Equivalence: All critical electrical parameters—contact form, coil voltage, switching voltage, and coil type—are identical between the original and substitute parts
  • Series Consistency: Both parts maintain the same Omron MY series designation, ensuring compatibility with existing relay base sockets and control circuit designs

Selection of the MY4-GS-R DC48 eliminates obsolescence risk while maintaining full functional compatibility with applications originally designed for the MY4-GS DC48.

Frequently Asked Questions (FAQ)

Q: Can the MY4-GS-R DC48 be used as a direct replacement for the MY4-GS DC48?

A: Yes. Both relays share identical contact form (4PDT), coil voltage (48VDC), switching voltage rating (250VAC, 220VDC max), and coil type (non-latching). The MY4-GS-R DC48 is the manufacturer-recommended substitute.

Q: What is the primary difference between these two relay models?

A: The MY4-GS-R DC48 features socketable mounting with plug-in quick connect termination (0.110" / 2.8mm), whereas the original MY4-GS DC48 mounting type is not specified. The substitute part also provides documented electrical specifications including coil current (18.8 mA), contact rating (6 A), and operating temperature range (-55°C ~ 70°C).

Q: Why is the original MY4-GS DC48 listed as obsolete?

A: The MY4-GS DC48 has reached end-of-life status in Omron's product portfolio. The MY4-GS-R DC48 represents the active production alternative within the same series.

Q: Are there any compliance differences between the two parts?

A: The MY4-GS DC48 carries RoHS Compliant status, while the MY4-GS-R DC48 meets the more stringent ROHS3 Compliant standard. Both parts satisfy environmental and regulatory requirements for industrial applications.

Q: What termination style does the substitute part use?

A: The MY4-GS-R DC48 uses plug-in quick connect termination with 0.110" (2.8mm) connectors, enabling rapid installation and removal from relay bases.

Q: Is the contact material specified for the original part?

A: The original MY4-GS DC48 contact material is not specified in the available documentation. The MY4-GS-R DC48 uses silver (Ag) contact material, which is standard for general purpose relays in this voltage and current class.

Request Quote (Ships tomorrow)