Request Quote
(Ships tomorrow)
Circuit Breaker Thermal Magnetic 30A 4420.0876
Part Overview
The SCHURTER 4420.0876 is a single-pole thermal magnetic circuit breaker rated for 30A at 180 V DC with lever actuation and DIN rail mounting. This component is classified as obsolete, making substitute parts necessary for new designs and ongoing system maintenance. The breaker provides overcurrent and thermal protection in DC applications requiring CSA, EN, GB, IEC, and UL certifications.
Substiute Parts
Key Parameters
| Parameter | Value |
|---|---|
| Manufacturer Part Number | 4420.0876 |
| Manufacturer | SCHURTER Inc. |
| Series | AS168XDC1 |
| Product Status | Obsolete |
| Mounting Type | DIN Rail |
| Breaker Type | Thermal Magnetic |
| Current Rating | 30A |
| Voltage Rating - DC | 180 V |
| Actuator Type | Lever |
| Number of Poles | 1 |
| Approval Agencies | CSA C22.2 No 14, CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, UL1077, UL508 |
| RoHS Status | ROHS3 Compliant |
Substitute Part Grouping Explanation
Substitution for the SCHURTER 4420.0876 is determined by the following critical parameters:
- Current Rating: 30A (exact match required)
- Breaker Type: Thermal Magnetic (exact match required)
- Mounting Type: DIN Rail (exact match required)
- Actuator Type: Lever (exact match required)
- Number of Poles: 1 (exact match required)
- Voltage Compatibility: The substitute must operate at voltage ratings that encompass or exceed the original 180 V DC specification
- Approval Certifications: Compliance with relevant safety standards (UL, CSA, IEC, EN, GB)
The Altech Corporation 1D30UL meets these substitution criteria with identical current rating, breaker type, mounting configuration, and pole count. The substitute operates at 277 V AC/DC, which provides voltage compatibility for DC applications at 180 V.
Parameter Comparison
| Parameter | SCHURTER 4420.0876 | Altech 1D30UL |
|---|---|---|
| Manufacturer | SCHURTER Inc. | Altech Corporation |
| Mounting Type | DIN Rail | DIN Rail |
| Breaker Type | Thermal Magnetic | Thermal Magnetic |
| Current Rating (Amps) | 30A | 30A |
| Voltage Rating | 180 V DC | 277 V AC/DC |
| Actuator Type | Lever | Lever |
| Number of Poles | 1 | 1 |
| Product Status | Obsolete | Active |
| Approval Agencies | CSA C22.2 No 14, CSA C22.2 No 235, EN 60934, GB 17701, IEC 60934, UL1077, UL508 | CE, cULus, UL489 |
| RoHS Status | ROHS3 Compliant | ROHS3 Compliant |
Engineering Selection Recommendations
The Altech 1D30UL is an active product suitable for replacing the obsolete SCHURTER 4420.0876 in new designs and system upgrades. Both components share identical functional specifications: 30A thermal magnetic protection, single-pole configuration, lever actuation, and DIN rail mounting.
The substitute carries cULus and UL489 certifications, providing North American compliance. The original part's broader certification portfolio (EN 60934, GB 17701, IEC 60934) should be verified against specific regional requirements for the application. The Altech component's 277 V AC/DC rating accommodates the original 180 V DC specification with adequate voltage margin.
Frequently Asked Questions (FAQ)
Q: Can the Altech 1D30UL directly replace the SCHURTER 4420.0876?
A: Yes, for applications requiring 30A thermal magnetic protection on DIN rail with lever actuation. Both components are single-pole breakers with identical current ratings and mounting configurations. Verify that the substitute's certification profile (CE, cULus, UL489) meets your regional compliance requirements.
Q: What is the voltage compatibility between these two breakers?
A: The SCHURTER 4420.0876 is rated for 180 V DC. The Altech 1D30UL is rated for 277 V AC/DC, which encompasses the original voltage specification. The substitute operates safely at 180 V DC applications.
Q: Why is the original SCHURTER part obsolete?
A: The SCHURTER 4420.0876 is classified as obsolete, indicating it is no longer in active production. The Altech 1D30UL is an active product with current manufacturing and availability.
Q: Are there packaging differences between these parts?
A: The SCHURTER 4420.0876 is packaged as individual units. The Altech 1D30UL is supplied in bulk packaging. Confirm packaging requirements for your procurement process.
Q: Do both breakers meet the same safety standards?
A: The SCHURTER part carries CSA, EN, GB, IEC, and UL certifications. The Altech substitute carries CE, cULus, and UL489 certifications. Both are ROHS3 compliant. Verify that the substitute's certification set aligns with your application's regional and industry standards.
Alternative Parts
SJ6012L2TP
Littelfuse Inc.
6 Alternative Parts
JMK107BBJ476MA-RE
Taiyo Yuden
10 Alternative Parts
GMK107BBJ475MA-T
Taiyo Yuden
5 Alternative Parts
SJ6020N2ARP
Littelfuse Inc.
3 Alternative Parts
SJ6025R2ATP
Littelfuse Inc.
4 Alternative Parts
2474-05L
API Delevan Inc.
1 Alternative Parts
4590R-684K
API Delevan Inc.
1 Alternative Parts
CM6560R-334
API Delevan Inc.
1 Alternative Parts
CM6460-104
API Delevan Inc.
1 Alternative Parts
5526-12
API Delevan Inc.
1 Alternative Parts