Phoenix Contact 1826306 Terminal Block Plug - Equivalent & Substitute Parts

Part Overview

The Phoenix Contact 1826306 is a 4-position terminal block plug with female sockets, 0.200" (5.08mm) pitch, and 225° free-hanging wire entry orientation. This component is classified as an active product and is used in industrial control and power distribution applications requiring screw-type termination with rising cage clamp technology. Substitute parts are identified when equivalent electrical ratings, mechanical compatibility, and termination methods align with the original specification, enabling direct replacement in applications where wire entry angle and housing material variations are acceptable.

Substiute Parts

1826306
Phoenix ContactIn Stock: 11131826306 Datasheet
1826306
Current Part
796634-4
TE Connectivity AMP ConnectorsIn Stock: 2002796634-4 Datasheet
796634-4
Similar

Key Parameters

Parameter Value
Manufacturer Part Number 1826306
Manufacturer Phoenix Contact
Category Terminal Blocks
Type Plug, Female Sockets
Number of Positions 4
Pitch 0.200" (5.08mm)
Plug Wire Entry 225°
Termination Style Screw - Rising Cage Clamp
Current - UL 15 A
Voltage - UL 300 V
Wire Gauge Range - AWG 12-30 AWG
Wire Gauge Range - mm² 0.2-2.5mm²
Screw Size M3
Material Flammability Rating UL94 V-0
RoHS Status ROHS3 Compliant
Product Status Active

Substitute Part Grouping Explanation

Substitution of the Phoenix Contact 1826306 is based on the following critical parameters that must align between the main part and substitute:

  • Electrical Compatibility: Current rating (UL: 15 A minimum), voltage rating (UL: 300 V minimum), and wire gauge acceptance (12-30 AWG or 0.2-2.5mm² minimum range)
  • Mechanical Compatibility: 4-position configuration, 0.200" (5.08mm) pitch, female socket type, and screw-type rising cage clamp termination
  • Physical Form Factor: Free-hanging (in-line) mounting type, M3 screw size, and insulation height of 0.610" (15.49mm)
  • Regulatory Compliance: UL94 V-0 flammability rating and ROHS3 compliance

The substitute part TE Connectivity AMP Connectors 796634-4 meets these core substitution criteria. The primary difference is the wire entry angle (180° versus 225°), which represents a mechanical orientation variation acceptable in applications where the connector orientation can be adjusted to accommodate the straight wire entry configuration.

Parameter Comparison

Parameter Phoenix Contact 1826306 TE Connectivity 796634-4 Compatibility Notes
Number of Positions 4 4 Identical
Pitch 0.200" (5.08mm) 0.200" (5.08mm) Identical
Type Plug, Female Sockets Plug, Female Sockets Identical
Termination Style Screw - Rising Cage Clamp Screw - Rising Cage Clamp Identical
Plug Wire Entry 225° 180° Different orientation; mechanical adjustment may be required
Current - UL 15 A 15 A Identical
Voltage - UL 300 V 300 V Identical
Wire Gauge Range - AWG 12-30 AWG 12-30 AWG Identical
Wire Gauge Range - mm² 0.2-2.5mm² 0.05-3mm² Substitute accepts wider range
Screw Size M3 M3 Identical
Insulation Height 0.610" (15.49mm) 0.610" (15.49mm) Identical
Material Flammability Rating UL94 V-0 UL94 V-0 Identical
RoHS Status ROHS3 Compliant ROHS3 Compliant Identical
Mounting Type Free Hanging (In-Line) Free Hanging (In-Line) Identical
Color Green Green Identical
Contact Mating Finish Tin Tin Identical
Features Retention Latches (Non-Wire Side) Retention Latches (Non-Wire Side) Identical

Engineering Selection Recommendations

The TE Connectivity AMP Connectors 796634-4 is a qualified substitute for the Phoenix Contact 1826306 based on the following engineering criteria:

Electrical Equivalence: Both components maintain identical UL current (15 A) and voltage (300 V) ratings, ensuring no degradation in electrical performance. The substitute's expanded wire gauge acceptance (0.05-3mm²) provides additional flexibility without compromising the original 0.2-2.5mm² specification range.

Mechanical Equivalence: Both components feature identical 4-position, 0.200" (5.08mm) pitch configurations with screw-type rising cage clamp termination and M3 screw sizing. The insulation height and mounting type are identical, supporting direct mechanical integration.

Regulatory Compliance: Both components carry ROHS3 compliance and UL94 V-0 flammability ratings, meeting identical regulatory requirements for industrial applications.

Primary Consideration: The wire entry angle differs (225° versus 180°). This represents a mechanical orientation variation that requires assessment of the specific application layout. In applications where connector orientation can be adjusted or where straight wire entry is acceptable, this substitute provides full functional equivalence.

Product Status: Both components are active products with confirmed inventory availability, supporting supply chain continuity.

Frequently Asked Questions (FAQ)

Q: Can the TE Connectivity 796634-4 directly replace the Phoenix Contact 1826306 without any modifications?

A: Electrical and mechanical compatibility is confirmed. The primary consideration is the wire entry angle: the Phoenix Contact uses 225° entry while the TE Connectivity uses 180° entry. If your application layout accommodates straight wire entry or allows connector repositioning, direct replacement is feasible. If the 225° angle is a critical design requirement, physical layout verification is necessary.

Q: Are the electrical ratings identical between these two parts?

A: Yes. Both components are rated for 15 A (UL) and 300 V (UL). Wire gauge acceptance ranges are compatible, with the TE Connectivity part accepting a slightly wider range (0.05-3mm² versus 0.2-2.5mm²).

Q: Do both parts meet the same regulatory standards?

A: Yes. Both components are ROHS3 compliant and carry UL94 V-0 flammability ratings, meeting identical regulatory requirements for industrial control and power distribution applications.

Q: What is the significance of the different wire entry angles?

A: The 225° angle on the Phoenix Contact provides angled wire entry, while the 180° angle on the TE Connectivity provides straight wire entry. This is a mechanical orientation difference that affects how wires are routed into the connector. Application layout and wire routing requirements determine whether this difference impacts usability.

Q: Are the screw termination specifications the same?

A: Both components use M3 screws with rising cage clamp termination. The Phoenix Contact specifies 0.5-0.6 Nm torque while the TE Connectivity specifies 0.79 Nm. Both values are within acceptable ranges for M3 screw termination in terminal block applications.

Q: Can I use the TE Connectivity part for wire gauges smaller than 0.2mm²?

A: The TE Connectivity part accepts wire gauges down to 0.05mm², which exceeds the original Phoenix Contact specification of 0.2mm² minimum. However, if your application requires the original 0.2mm² minimum specification, verify that smaller gauges are not used in your circuit design.

Request Quote (Ships tomorrow)